NOTE: anything in parenthesis is an example value, replace with a value needed for your project.
- Define a variable in your IEC program. A floating point (SP), not retained, Input.
- Create (if not already) an IO channel, Float, Input (i.e., #1)
- Modify the Parameters of the selected Input(#1) of the channel to 255.253.1 i.e., Indirect
- Map the IO channel to the IEC variable (SP)
- Set the global variable NUMREGISTERS to (1).
| Variable | Name | Value | Parameter |
| ISaGRAF Variable | SP | 13.57 | User:9012 |
| IO channel | tx.y | SP | 255.253.1 |
| Totalflow Register | 91.9.18 | 13.57 | |
| Indirect | 91.253.1 | 7.4.1 | |
| IO/AI1 | 7.4.1 | 13.57 |
ReplyDeleteمدثر راناDecember 30, 2014 at 10:52 PM
Dear Sir,
I am writing you to seek assistance and guidance for downloading IEC application file to a XRC.
The project was commissioned in 2007 and running successfully over the period of time.
Some of our RTU units were damaged and unable to perform the tasks.
We want to brought a spare RTU into service to replace an existing RTU.
A message device was not made for this version application was shown while we try to download the IEC binary file into XRC.
Following are the supporting files
INI file for IEC application.
bin File for downloading via IEC downloader.
S19 file for flash downloading.
I will be waiting for your kind support.
Thanks and Regards
Sounds as though you replaced a G3 with a G4. ISaGRAF is not binary compatible between generations. A recompile would be necessary. Please contact you salesman for support. We do not provide support on the unofficial blog.